EPA Section 608 (Core, Type I, II, III, Universal) practice test

180 free practice questions for this exam, each with the reason for the answer and where to look it up.

Beta. These questions are new. They were written and checked with AI and have not yet been reviewed by a licensed tradesperson. If one looks wrong, use “Report this question” and we will fix it.

EPA 608 certification: practice test

10 questions, graded as you go, with the reason for every answer. No sign-up.

Practice tests that prepare you for this exam

About the exam

ExamEPA Section 608 (Core, Type I, II, III, Universal)
Who runs itEPA-approved certifiers
WhereUnited States

Question count, time limit and pass mark differ by where you take it. Check the official candidate bulletin from the organisation that runs your exam.

Sample questions

Why do HCFCs do less damage to the ozone layer than CFCs?

  1. The hydrogen in the molecule lets it break down lower in the atmosphere
  2. The fluorine in the molecule cancels out the effect of the chlorine atoms
  3. HCFC molecules are too heavy to rise above the troposphere
  4. HCFC molecules contain bromine in place of the chlorine
Show the answer

A. The hydrogen in the molecule lets it break down lower in the atmosphere

Hydrogen makes an HCFC molecule less stable, so most of it breaks down before reaching the stratosphere and less chlorine arrives there. Fluorine does not neutralize chlorine, and molecular weight does not keep refrigerants out of the stratosphere.

Reference: EPA Section 608 Core

A technician who holds only Type I certification is asked to recover the refrigerant from a 3-ton residential split system. The technician

  1. may do the work, because the charge is under 15 lb
  2. may do the work if a self-contained machine is used
  3. may not do the work, because it requires Type II certification
  4. may not do the work, because it requires Type III certification
Show the answer

C. may not do the work, because it requires Type II certification

A split system is not a small appliance, so Type I does not cover it; R-22 and R-410A split systems are high-pressure appliances under Type II. The size of the charge alone does not make something a small appliance.

Reference: 40 CFR 82.161

Type II certification covers which equipment?

  1. Low-pressure centrifugal chillers and the purge units that are fitted to them
  2. Factory-sealed appliances that hold five pounds of refrigerant or less
  3. Motor vehicle air conditioners and the MVAC-like systems on farm equipment
  4. Medium-, high- and very high-pressure appliances other than small appliances and MVACs
Show the answer

D. Medium-, high- and very high-pressure appliances other than small appliances and MVACs

Type II covers medium-, high- and very high-pressure appliances, except small appliances (Type I) and motor vehicle systems (Section 609). Low-pressure chillers fall under Type III.

Reference: 40 CFR 82.161

Taking this exam?

Tell us where and when you are taking it, and what you want more of. It decides what we write next.

Other hvac & refrigeration exams with practice tests

EPA Section 609 motor vehicle air conditioning · HVAC / mechanical journeyman · HVAC / mechanical contractor · NATE Ready-to-Work and HVAC Support · NATE air conditioning service and installation · NATE heat pump service and installation · NATE gas heating service and installation · Refrigeration journeyman / operating engineer · RSES CM / CMS