Mixed practice test

10 questions, graded as you go, with the reason for every answer. No sign-up.

Timed mock exam

50 questions in 60 minutes, drawn from every topic. No answers shown until the end, then a score, your weakest topics and a review of what you missed.

Practise by topic

Sample questions

Using the nominal 400 CFM per ton, how much airflow does a 3-ton air conditioner need?

Answer in CFM.

Show the answer

1200 CFM

Airflow = tons x 400 CFM per ton = 3 x 400 = 1,200 CFM.

Reference: Nominal airflow per ton of cooling

A heating element with a resistance of 12 ohms is connected to 240 V. How much current does it draw?

Answer in A.

Show the answer

20 A

I = E / R = 240 V / 12 ohms = 20 A.

Reference: Ohm's law

A furnace has 68°F return air and 125°F supply air. What is the temperature rise?

Answer in °F.

Show the answer

57 °F

Temperature rise = supply air temperature - return air temperature = 125°F - 68°F = 57°F.

Reference: Furnace temperature rise

An air conditioner delivers 36,000 Btu/h while drawing 3,000 W at the rating condition. What is its EER?

Answer in Btu/Wh.

Show the answer

12 Btu/Wh

EER = cooling output in Btu/h / power input in watts = 36,000 / 3,000 = 12.

Reference: Energy efficiency ratio

What leaves the outlet of the metering device and enters the evaporator?

  1. A cold low-pressure vapor with several degrees of superheat
  2. A warm high-pressure liquid with several degrees of subcooling
  3. A cold low-pressure mix of liquid and some flash gas
  4. A cold low-pressure liquid with no vapor present at all
Show the answer

C. A cold low-pressure mix of liquid and some flash gas

The pressure drop across the metering device makes part of the liquid flash to vapor, which cools the rest to the evaporator saturation temperature, so a mostly liquid mixture enters the coil. It is not superheated vapor yet; superheat is only picked up near the evaporator outlet after all the liquid has boiled.

Reference: Metering devices; flash gas

Exams this helps with

ExamWho runs itWhere
HVAC / mechanical journeyman readyState and local boardsUnited States (varies by state)
HVAC / mechanical contractor readyState boardsUnited States (varies by state)
NATE Ready-to-Work and HVAC Support readyNATEUnited States
NATE air conditioning service and installation readyNATEUnited States
NATE heat pump service and installation readyNATEUnited States
NATE gas heating service and installation readyNATEUnited States

Tell us what to improve · More hvac & refrigeration practice